SF6T-004 is a high-performance portable device that integrates SF6 micro-water detection, purity analysis, and decomposition product testing. It completes three key indicators in one measurement, saves 2/3 of gas consumption, and improves on-site detection efficiency by 300%. It is suitable for power equipment maintenance and laboratory precision analysis.
Item No. :
SF6T-004Minimum Order Quantity (MOQ) :
1 SetPayment Method :
L/C, T/TPrice :
NegotiatableProduct Origin :
ChinaSupply Ability :
10 Set per monthLead Time :
90 DaysConventional packaging :
PlywoodPortable SF6 Gas Comprehensive Analyzer Compliant With Iec 60480 And Astm D2029
SF6 Testing Equipment
Product Introduction
SF6T-004 SF6 gas comprehensive analyzer breaks through the limitations of traditional single-function detection and integrates the core technologies of micro-water meter, purity meter and decomposition product analyzer. Through the optimization of gas path design and intelligent algorithm, a single measurement takes only 8 minutes, and synchronously outputs dew point (-80~+20℃), SF6 purity (0~100%), SO₂/H₂S content (0~100ppm) and other data, greatly reducing equipment exhaust loss and ensuring safe operation of the power grid.
Product Features
✅ Efficient three-in-one detection
Single inflation completes three tests of trace water, purity, and decomposition, and gas consumption is reduced by 67%
✅ Extremely fast response
Dew point measurement ≤5min | Purity & decomposition ≤3min
✅ Military-grade air tightness
Self-locking joints imported from Germany, leakage rate <0.5%
✅ Intelligent data management
200 sets of storage + visual tracking of dew point curves
✅ Full parameter direct reading
4.3-inch LCD real-time display of dew point, ppm, SO₂, H₂S, temperature and humidity
✅ Ultra-long battery life
4Ah lithium battery supports 10 hours of continuous operation
International reference standards
Product Use
✅ GIS switchgear/circuit breaker maintenance
✅ Transformer SF6 gas quality monitoring
✅ High-voltage laboratory gas acceptance test
✅ Preventive maintenance of power equipment
✅ Environmental protection department decomposition emission detection
Test objects and items
Objects: SF6 gas (pure gas, mixed gas), SF6 in power equipment, industrial SF6 mixture.
Items: trace water content, SF6 purity, SO₂ content, H₂S content, ambient temperature and humidity (auxiliary analysis).
Parameter | Specification | Accuracy |
Dew Point Range | -80℃ to +20℃ | ±0.5℃ |
Moisture Measurement | 0-2000 ppm | ±1% FS |
SF6 Purity | 0-100% | ±0.1% |
SO₂ Detection | 0-100 ppm | ±0.5 ppm |
H₂S Detection | 0-100 ppm | ±0.5 ppm |
Response Time | Dew Point: ≤5 min Purity/Decomposition: ≤3 min |
- |
Data Storage | 200 sets (with timestamp) | - |
Display | 4.3-inch color LCD | - |
Power Supply | Built-in Li-ion (10h) AC 100-240V |
- |
Gas Interface | German auto-lock fittings (Hauber®) | Leakage <0.5% |
Operating Temperature | -30℃ to +50℃ | - |
Communication | USB/Bluetooth data export | - |
Weight | 3.2 kg (with battery) | - |
Dimensions | 280×220×110 mm (W×H×D) | - |
Calibration Cycle | Recommended 12 months | NIST traceable |
Hot Tags :